Customization: | Available |
---|---|
Application: | High-performance Transducer, Three Phase Transducer, General Transducer, High Frequency Converter Transducer |
Output Type: | Triple |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Multiple inverter basic protection functions;Water pump exclusive protection function(water shortage protection,high and low pressure protection,leakage protection,anti-freeze embroidery protection, sensor disconnection protection).
1. The pressure of the pipe network is detected by the host and sent to the auxiliary machine. When the pressure is not enough, the auxiliary machine starts and runs according to the set frequency, and the main machine performs constant pressure PID adjustment.
2. The main and auxiliary machines altemately run in sequence at regular intervals to realize the uniform use of the water pump and extend the life of the water pump.
Perfectly drive a variety of water pump motors such as asynchronous, permanent magnet synchronous, synchronous reluctance, etc.
>>> Industrial Applications for GS20 General Pump Drive
Applications: Farmland irrigation, residential water, landscape fountains, swimming pool water supply, desert management.
Projects | specifications | ||
Power input | Voltage, frequency | Single phase :220V 50/60Hz;Three phase: 220V 50/60Hz; Three phase 380V 50/60Hz , | |
Allowable fluctuations | voltage unbalance rate:<3%; Frequency:±5%; aberration rate: as IEC61800-2 required | ||
Inrush current | Lower than rated current | ||
Power factor | ≥0.94(with DC reactor) | ||
Efficiency | ≥96% | ||
Output | Output voltage | Output under rated condition: 3 phase, 0~input voltage, deviation<5% | |
Output frequency range | G type:0~600Hz | ||
Output frequency accuracy | Max frequency ±0.5% | ||
Overload capacity | G type: 150% rated current/1 min, 180% rated current/10s, 200% rated current/0.5s | ||
P type: 120% rated current/1 min, 140% rated current/10s, 150% rated current/0.5s | |||
Main control performance | Motor type | Three-phase asynchronous motor; Permanent magnet synchronous motor (sine wave) | |
Control mode | V/F control, Open loop vector control, Closed loop vector control | ||
Modulation | Optimizing Space Voltage Vector PWM Modulation | ||
Carrier frequency | 1.0~16.0kHz | ||
Speed control range | VC without PG: rated load 1:100; VC with PG: rated load 1:1000 | ||
Steady speed accuracy | VC without PG: ≤2% rated synchronized speed; VC with PG: ≤0.05% rated synchronized speed | ||
Starting torque | VC without PG: 150% rated torque at 0.5Hz; VC with PG: 0Hz, 200% rated torque at 0Hz | ||
Torque response | VC without PG:<20ms; VC with PG: <10ms | ||
Frequency accuracy | Digital setting: max frequency×±0.01%; Analog setting: max frequency×±0.2% | ||
Frequency resolution | Digital setting: 0.01Hz; Analog setting: max frequency×0.05% | ||
Basic functions | Torque control | Torque setting calculation, torque mode speed limit | |
DC braking capacity | Starting frequency:0.00~50.00Hz; Braking time:0.0~60.0s; Braking current:0.0~150.0% rated current | ||
Torque boost capacity | Automatic torque boost 0.0%~100.0%; Manual torque boost 0.0%~30.0% | ||
V/F curve | Four modes: linear torque characteristic curve, self-set V/F curve, torque reduction characteristic curve (1.1 to 2.0 power), square V/F curve | ||
Acceleration/Deceleration curve | 2 modes: linear Acceleration/Deceleration and S curve Acceleration/Deceleration. 4 sets of ACC/DEC, time unit 0.01s selectable, longest time: 650.00s. | ||
Rated output voltage | Using the power supply voltage compensation function, the rated voltage of the motor is 100%, which can be set within the range of 50 to 100% (the output cannot exceed the input voltage) | ||
Voltage auto-adjustment | While power supply voltage fluctuates, it can auto-keep constant output voltage. | ||
Auto energy-saving running | While under V/F control mode, according to load situation, auto-optimize output voltage to save energy. | ||
Auto-limit current | Auto-limit the current while running to prevent over current break trouble. | ||
Instant power off treatment | Uninterrupted operation through bus voltage control during instantaneous power loss | ||
Standard functions | PID control, speed track, power off restart, jump frequency, upper/lower frequency limit control, program operation, multi- speed, RS485, analog output, frequency impulse output. | ||
Frequency setting channels | Keyboard digital setting, Analog voltage/current terminal AI1, Analog voltage/current terminal AI2, Communication given and multi-channel terminal selection, Main and auxiliary channel combination, expansion card, supporting different modes switch | ||
Feedback input channel | Voltage/Current Terminal AI1, Voltage/Current Terminal AI12, Communication given, Low-speed pulse input PUL, extension card | ||
Running command channel | Operation panel given, external terminal given, communication given, expansion card given | ||
Input command signal | Start, stop, FWD/REV, JOG, multi-step speed, free stop, reset, ACC/DEC time selection, frequency given channel selection, external fault alarm. | ||
External output signal | 1 relay output, 1 collector output, 1 AO output: 0~10V output or 4~20mA output | ||
Protection function | Overvoltage, under-voltage, current limit, over-current, overload, electric thermal relay, overheat, overvoltage stall, data protection, rapid speed protection, input/output phase failure protection | ||
Keyboard display | LED display | Built-in keyboard: single line 5- digital tube display | monitor 1 inverter status quantity |
External keyboard: double line 5- digital tube display | Monitor 2 inverter status quantities | ||
Parameter copy | Upload and download function code information of the inverter for fast parameter copying | ||
Status monitor | Output frequency, given frequency, output current, input voltage, output voltage, motor speed, PID feedback, PID given value, module temperature etc. monitor parameters. | ||
Error alarm | Over-voltage, under-voltage, over-current, short circuit, phase failure, overload, overheat, overvoltage stall, current limit, or Data protection compromised, current fault health, historical fault record | ||
Environment | Install place | The altitude is less than 1000 meters, and the derating is more than 1000 meters. The derating is 1% for every 100 meters. No condensation, icing, rain, snow, hail, etc., solar radiation is less than 700W/m2, air pressure 70~106kPa | |
Temperature, humidity | -10 ~ +50°C, derating can be used above 40 °C, the maximum temperature is 60 °C (no-load operation), 5%~95%RH(no condensation) | ||
5% to 95% RH (no condensation) | |||
Vibration | 9~200Hz,5.9m/s2(0.6g) | ||
5%-95%RH (no condensation) | |||
Storage temperature | -30-+60ºC | ||
Installation | Wall hanging | ||
Protection degree | IP20 | ||
Cooling method | Forced air cooling |